Skip to main content
KLAE PLT
ICC 221-K1-01-D1 K-Type 0-200 4/20mA Upscale Converter

Industrial Control & Instrumentation

ICC 221-K1-01-D1 K-Type 0-200 4/20mA Upscale Converter

Brand:
Eaton/MTL
Model:
221-K1-01-D1
New No warranty — sold as-is

RM 335.40

Only 1 left in stock

Enquire First
Order via WhatsApp

Collection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.

Description

The ICC221 temperature converter accepts low-level dc signals from a thermocouple and converts these into a proportional 4 to 20mA output. This unit is factory-configured for a K-type thermocouple over a 0 to 200°C range (input code K1), with a 4 to 20mA output (O1) and an upscale safety drive on thermocouple burnout (D1). Built-in cold-junction compensation and galvanic isolation between input and output eliminate earthing and ground-loop problems.

Specifications

Number of channels One
Input signal (configured) K-type thermocouple, 0 to 200°C (input code K1)
Input current (upscale) <150nA
Output signal (configured) 4 to 20mA (output code O1)
Isolation between input and output 1500V dc/ac
Power supply required Vs min = 17 + (RL x 0.02)V dc Vs max = 35V dc
Maximum load (RL, current only) 50(Vs–17)Ω
Zero adjustment Approximately ±2.5% of span
Span adjustment Approximately ±2.5% of span
Transfer accuracy at 25°C (THC input, including non-linearity and hysteresis) Within 0.1% of span ±1°C
Temperature drift (span) ±0.005% of input span/°C
Temp drift (suppression/elevation [E]) ±0.01% of E/°C
Temperature drift (zero, THC input, except type R) ±0.01% of span/°C or ±0.03°C/°C, whichever is greater
Response time To reach 90% of span: 40ms To reach 99.9% of span: 250ms
Safety drive on THC burnout (upscale) >21mA; 29mA maximum
Common mode rejection ratio 150dB typical
RFI susceptibility Conforms to IEC801.3
Ambient temperature limits -20°C to +55°C (operating) -40°C to +80°C (storage)
Humidity 5 to 95% RH, non-condensing
Terminals Accommodate 2.5mm² conductors
Casing 25mm width polyamide casing
Mounting Directly onto T- or G-section DIN-rail to DIN46277