Collection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.

Description

The ICC312 is an independently powered isolator providing a fully isolated dc supply for a 2-wire transmitter while transferring the transmitter current to two separate isolated 4 to 20mA output circuits driving loads up to 1kΩ. An isolated line-fault detection (LFD) output is provided via open collector, which turns off if the input cable is broken.

Specifications

Number of input channels One (either terminals 7 & 8 or 8 & 9)
Input channel (terminals 7 & 8) 2-wire transmitter supply: 4 to 20mA
Input channel (terminals 8 & 9) 4 to 20mA current source
Number of output channels Two
Isolation between input, output 1, output 2 and power supply 1500V dc/ac
Power supply 20 to 35V dc
Voltage available for transmitter 20V minimum at 20mA
Voltage drop across input from current source (terminals 8 & 9) 2.4V maximum
Power requirements (supplying a transmitter) 150mA maximum at 20V dc with a 20mA signal 120mA maximum at 35V dc with a 20mA signal
Power requirements (from a current source) 110mA maximum at 20V dc with a 20mA signal 90mA maximum at 35V dc with a 20mA signal
Load resistance 0 to 1kΩ
Transfer accuracy at 25°C for both outputs Better than 20µA
Line-fault detection (LFD) output Transistor open collector output
Response time To reach 90% of span: 80ms To reach 99.9% of span: 280ms
Temperature drift <1µA/°C
Common mode rejection ratio 150dB typical
RFI susceptibility Conforms to IEC801.3
Ambient temperature limits -20°C to +55°C (operating) -40°C to +80°C (storage)
Humidity 5 to 95% RH, non-condensing
Terminals Accommodate 2.5mm² conductors
Casing 40mm width polyamide casing
Mounting Directly onto T- or G-section DIN-rail to DIN46277