Skip to main content
KLAE PLT
ICC 241-T3 Passive Isolator

Industrial Control & Instrumentation

ICC 241-T3 Passive Isolator

Brand:
Eaton/MTL
Model:
241-T3
New No warranty — sold as-is

RM 167.70

Only 2 left in stock

Enquire First
Order via WhatsApp

Collection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.

Description

The ICC241 is a loop-powered isolator with a number of possible applications, including isolating and repeating a 4 to 20mA signal from a controller to drive an I/P converter, or isolating the signal from a transmitter. This unit is the T3 variant, rated for loads up to 600Ω and fitted with a load-trimming potentiometer for optimising accuracy across load changes. Galvanic isolation between input and output simplifies interface wiring by eliminating earthing and ground-loop problems.

Specifications

Number of channels One
Input signal 4 to 20mA
Output signal 4 to 20mA
Isolation between input and output 1500V dc/ac
Maximum input voltage (output open circuit or >700Ω) 24V typical
Voltage drop across isolator (Vin) <4.9V (T3 option) including test resistors, plus voltage drop across the load
Load (RL) range for specified performance (T3) 100 to 600Ω
Transfer accuracy at 25°C (including non-linearity and hysteresis) Better than 20µA
Temperature drift <0.01% of span/°C
Response time To reach 90% of span: 40ms To reach 99.9% of span: 100ms
Common mode rejection ratio 150dB typical
RFI susceptibility Conforms to IEC801.3
Ambient temperature limits -20°C to +55°C (operating) -40°C to +80°C (storage)
Humidity 5 to 95% RH, non-condensing
Terminals Accommodate 2.5mm² conductors
Casing 25mm width polyamide casing
Mounting Directly onto T- or G-section DIN-rail to DIN46277