Industrial Control & Instrumentation
MTL4014 Relay, 1-ch Swtch/Prox LFD
- Brand:
- Eaton/MTL
- Model:
- 4014
RM 536.40
5 units available
Order via WhatsAppCollection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.
Description
The MTL4014 enables a safe-area load to be controlled by a proximity detector or switch located in a hazardous area through a reed relay. Line faults are signalled through a separate reed relay. The line-fault detection (LFD) function can be used with both proximity detectors and switches, provided that for switches suitable resistors are added as shown in the circuit diagram. 'No-fail' earth-fault detection on either line can be provided by connecting an MTL4220 earth leakage detector to terminal 6.
Specifications
| Number of channels | One |
|---|---|
| Location of switch | Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location |
| Location of proximity detector | Zone 0, IIC, T4–6 if suitably certified Div.1, Group A, hazardous location |
| Voltage applied to sensor | 7.0V – 9.0V dc from 1kΩ nominal |
| Input/output characteristics | Output closed if input >2.1mA (<2kΩ) Output open if input <1.2mA (>10kΩ) Hysteresis: 200µA (650Ω) nominal |
| Line fault detection (LFD) | Line fault relay and channel relay open if input <50µA (broken line) or <100Ω (shorted line) |
| 'No-fail' earth fault protection | Enabled by connecting terminal 6 to an MTL4220 earth leakage detector Fault on either line proclaimed: unit continues working |
| Relay output characteristics | Single-pole on/off, open when relay de-energised Response time: 2ms maximum Contact rating: 10W, 0.5A, 35V (dc) Contact life expectancy: 10⁷ operations at maximum load |
| LED indicators | Amber: one provided for input, ON when output circuit is closed Red: one provided for LFD, ON when line fault is detected Green: one provided for power indication |
| Power requirement (Vs) | 45mA at 24V dc 50mA at 20V dc 36mA at 35V dc |
| Power dissipation within unit | 1.1W at 24V 1.3W at 35V |
| Isolation | 250V ac between safe and hazardous area circuits |
| Safety description | 10.5V, 800Ω, 14mA |
| FM entity parameters | Voc = 10.5V dc, Isc = 14mA, Ca = 2.4µF, La = 165mH |