Industrial Control & Instrumentation
MTL4015 Relay, 1-ch Switch/Prox
- Brand:
- Eaton/MTL
- Model:
- 4015
RM 187.80
Only 2 left in stock
Order via WhatsAppCollection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.
Description
With the MTL4015, a switch or proximity detector located in a hazardous area can control two safe-area loads through relays. A phase-reversal switch, located on top of the module, allows an alarm signal to be signalled for either state of the sensor. Line-fault detection (LFD) for broken or shorted lines is provided, along with facilities for earth-fault detection. Power and switch status are indicated by LEDs on top of the module.
Specifications
| Number of channels | One |
|---|---|
| Location of switches | Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location |
| Location of proximity detector | Zone 0, IIC, T4–6 if suitably certified Div.1, Group A, hazardous location |
| Voltage applied to sensor | 7.0–9.0V dc from 1kΩ |
| Input/output characteristics | Outputs closed if >2.1mA (<2kΩ) in sensor circuit Outputs open if <1.2mA (>10kΩ) in sensor circuit Hysteresis: 200µA (650Ω) nominal |
| Phase reversal | The operation of the output can be reversed by a switch on top of the unit |
| Line fault detection (LFD) | Output opens if input current <100µA (broken line) or >6.5mA (shorted lines) |
| 'No-fail' earth fault protection | Enabled by connecting terminal 6 to an MTL4220 earth leakage detector Fault on either line of each channel proclaimed: unit continues working |
| Relay output characteristics | Double-pole on/off, open when relay de-energised Response time: 2ms maximum Contact rating: 10W, 0.5A, 35V (dc) Contact life expectancy: 10⁶ operations at maximum load |
| LED indicators | Amber: one provided, ON when output circuit is closed Green: one provided for power indication |
| Power requirement (Vs) | 50mA at 24V dc 60mA at 20V dc 45mA at 35V dc |
| Power dissipation within unit | 1.2W at 24V 1.6W at 35V |
| Isolation | 250V ac between safe and hazardous area circuits |
| Safety description for each channel | 10.5V, 800Ω, 14mA |
| FM entity parameters | Voc = 10.5V dc, Isc = 14mA, Ca = 2.4µF, La = 165mH |