MTL4016 Relay, 2-ch Switch/Prox

Industrial Control & Instrumentation

MTL4016 Relay, 2-ch Switch/Prox

Brand:
Eaton/MTL
Model:
4016
New No warranty — sold as-is

RM 402.30

Only 3 left in stock

Enquire First
Order via WhatsApp

Collection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.

Description

With the MTL4016, two switches or proximity detectors located in a hazardous area can each control two safe-area loads. The four safe-area outputs are made through reed relays. Independent phase-reversal switches for each channel, located on top of the module, allow alarm signals to be signalled for either state of the sensors. Line-fault detection (LFD) for broken or shorted lines is provided, along with facilities for earth-fault detection. Power and switch status are indicated by LEDs on top of the module.

Specifications

Number of channels Two
Location of switches Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location
Location of proximity detector Zone 0, IIC, T4–6 if suitably certified Div.1, Group A, hazardous location
Voltage applied to sensor 7.0V – 9.0V dc from 1kΩ
Input/output characteristics Outputs closed if >2.1mA (<2kΩ) in sensor circuit Outputs open if <1.2mA (>10kΩ) in sensor circuit Hysteresis: 200µA (650Ω) nominal
Phase reversal The operation of each channel can be reversed by independent switches on top of the unit
Line fault detection (LFD) Outputs open if input current <100µA (broken line) or >6.5mA (shorted lines)
'No-fail' earth fault protection Enabled by connecting terminals 3 and 6 to an MTL4220 earth leakage detector Fault on either line of each channel proclaimed: unit continues working
Relay output characteristics Double-pole on/off, open when relay de-energised Response time: 2ms maximum Contact rating: 10W, 0.5A, 35V (dc) Contact life expectancy: 10⁶ operations at maximum load
LED indicators Amber: one provided for each channel, ON when output circuit is closed Green: one provided for power indication
Power requirement (Vs) 50mA at 24V dc 60mA at 20V dc 45mA at 35V dc
Power dissipation within unit 1.2W at 24V 1.6W at 35V
Isolation 250V ac between safe and hazardous area circuits
Safety description for each channel 10.5V, 800Ω, 14mA
FM entity parameters Voc = 10.5V dc, Isc = 14mA, Ca = 2.4µF, La = 165mH