MTL4021 Solenoid/Alarm Driver
- Brand:
- Eaton/MTL
- Model:
- 4021
RM 335.40
14 units available
Order via WhatsAppCollection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.
Description
The MTL4021 enables an on/off device in a hazardous area to be controlled by a volt-free contact or logic signal in the safe area. It can drive loads such as solenoids, alarms, LEDs and other low-power devices that are certified as intrinsically safe or classified as non-energy-storing simple apparatus. By connecting a second safe-area switch or logic signal, the output can be disabled — for example, to let a safety system override a control signal. Earth-fault detection can be provided by connecting an MTL4220 earth leakage detector to terminal 6.
Specifications
| Number of channels | One |
|---|---|
| Location of load | Zone 0, IIC, T4–6 hazardous area if suitably certified Div.1, Group A, hazardous location |
| Maximum output voltage | 25.5V from 232Ω |
| Output ripple | <0.5% of maximum output, peak-to-peak |
| Control input | Suitable for switch contacts, an open collector transistor or logic drive 0 = input switch closed, transistor on or <1.4V applied across terminals 10 & 11 1 = input switch open, transistor off or >4.5V applied across terminals 10 & 11 |
| Override input | An open collector transistor or a switch connected across terminals 8 and 9 can be used to turn the output off whatever the state of the control input 0 = transistor on or switch closed 1 = transistor off or switch open |
| Control / override logic | Control 0, Override 0 → Output off Control 0, Override 1 → Output on Control 1, Override 0 → Output off Control 1, Override 1 → Output off |
| Response time | Output within 10% of final value within 100ms |
| No-fail' earth fault protection | Enabled by connecting terminal 6 to an MTL4220 earth leakage detector Fault on either line proclaimed: unit continues working |
| LED indicators | Amber: one provided for status, ON when output circuit is active Green: one provided for power indication |
| Power requirement (Vs) | 100mA at 24V dc 120mA at 20V dc 75mA at 35V dc |
| Power dissipation within unit | 1.3W with typical solenoid valve, output on 1.9W worst case |
| Isolation | 250V ac between safe- and hazardous-area circuits |
| Safety description | 25.5V, 232Ω, 110mA |
| FM entity parameters | Voc = 25.5V dc, Isc = 110mA, Ca = 0.17µF, La = 3mH |