Order via WhatsAppCollection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.
Description
The MTL4024 (loop powered, for 24V systems) enables an on/off device in a hazardous area to be controlled by a 24V signal in the safe area. It can drive loads such as solenoids, alarms, LEDs and other low-power devices that are certified as intrinsically safe or classified as non-energy-storing simple apparatus. Provided that 24V dc is applied to the override input, the solenoid/alarm can be operated by a voltage change in the safe area; if the 24V dc override signal is removed, the solenoid/alarm turns off. Earth-fault detection can be provided by connecting an MTL4220 earth leakage detector to terminal 6.
Specifications
| Number of channels | One |
|---|---|
| Location of signal load | Zone 0, IIC, T4–6 hazardous area if suitably certified Div.1, Group A, hazardous location |
| Maximum output voltage | 25.5V from 232Ω |
| Output ripple | <0.5% of maximum output, peak-to-peak |
| Override input | A 24V signal applied across terminals 8 and 9 allows the solenoid/alarm to be operated by the supply across terminals 10 and 11. If the 24V signal is disconnected, the solenoid/alarm is off. <2.0V: Off >9.0V: Controlled by supply across terminals 10 and 11 >2.0V but <9.0V: Undetermined |
| Input impedance at terminal 8 | Typically 10kΩ |
| Response time | Output within 10% of final value within 100ms |
| 'No-fail' earth fault protection | Enabled by connecting terminal 6 to an MTL4220 earth leakage detector Fault on either line proclaimed: unit continues working |
| LED indicators | Amber: one provided for status, ON when output circuit is active Green: one provided for drive status, ON when supply is connected |
| Power requirement (control) | 100mA at 24V dc 120mA at 20V dc 75mA at 35V dc |
| Power dissipation within unit | 1.3W at 24V with typical solenoid valve, output on 1.9W worst case |
| Isolation | 250V ac between safe- and hazardous-area circuits |
| Safety description | 25.5V, 232Ω, 110mA |
| FM entity parameters | Voc = 25.5V dc, Isc = 110mA, Ca = 0.17µF, La = 3mH |