Industrial Control & Instrumentation
MTL4046P 4/20mA Driver, Smart
- Brand:
- Eaton/MTL
- Model:
- 4046P
RM 268.20
Only 1 left in stock
Order via WhatsAppCollection in Puchong, Selangor: collect your order from KLAE PLT, No. 53, Jalan Metro 1/1, Bandar Metro Puchong, 47160 Puchong, Selangor, Malaysia — or arrange your own courier or rider to collect it for you. Shipping & Collection Policy Payment: Pay online by FPX (online banking) through Billplz, or by bank transfer. Items in an unpaid order are reserved for 48 hours.
Description
The MTL4046P high-power isolating driver accepts a 4/20mA floating signal from a safe-area controller to drive a current/pressure converter (or any other floating load up to 870Ω) in a hazardous area. For HART® valve positioners, the module also permits bi-directional transmission of digital communication signals so the device can be interrogated either from the operator station or by a hand-held communicator (HHC). Process controllers with a readback facility can detect open or short circuits in the field wiring.
Specifications
| Number of channels | One |
|---|---|
| Location of I/P converter | Zone 0, IIC, T4–6 hazardous area if suitably certified Div.1, Group A, hazardous location |
| Working range | 4 to 20mA |
| Digital signal bandwidth | 500Hz to 10kHz |
| Maximum load resistance | 870Ω (17.4V at 20mA) |
| Minimum load resistance | 90Ω (short circuit detection at <50Ω) |
| Output resistance | >1MΩ |
| Under/over range capability | Under range = 1.0mA Over range = 26.0mA (load ≤600Ω) |
| Input and output circuit ripple | <40µA peak-to-peak |
| Transfer accuracy at 20°C | Better than 20µA |
| Input characteristics | <4.0V with the field wiring intact <0.9mA with the field wiring open- or short-circuit |
| Response time | Settles within 200µA of final value within 100ms |
| Temperature drift | <1.0µA/°C |
| Power requirement (Vs) | 58mA at 24V dc 70mA at 20V dc 40mA at 35V dc |
| Power dissipation within unit | 1.2W typical at 24V with 20mA loop current 1.4W worst case |
| Isolation | 250V ac between safe- and hazardous-area circuits Input circuit is floating |
| Safety description | 28V, 240Ω, 116mA, Um = 250V rms or dc |
| FM entity parameters | Vt = 28V dc, Isc = 117mA, Ca = 0.14µF, La = 2.6mH |